Step 1: Enter Settings Mode
Press and hold the test switch for more than 4 seconds. The fitting will enter Settings Mode. Settings Mode has a 5 second entrance and will time out after 5 seconds of inactivity, so complete the next step promptly.
Step 2: Press the test switch the required number of times
Each press should be 0.5 to 2 seconds on and 0.5 to 2 seconds off. Allow a minimum settling time of 10 seconds between settings changes.
| Presses | Function | LED Confirmation |
|---|---|---|
| 3 presses | Activate SafeTest and start an immediate duration test | 3 x amber flash |
| 5 presses | Activate SafeTest (no duration test) | 5 x amber flash |
| 7 presses | Turn off SafeTest | 7 x amber flash |
| 9 presses | Clear last test result | 9 x amber flash |
The amber flash sequence repeats for 20 seconds, allowing a visual check that the command was accepted.
Other test switch functions (normal mode)
| Action | Function |
|---|---|
| Hold less than 4 seconds | Start a function test |
| Hold more than 10 seconds | Start a duration test (or exit a duration test if one is running) |
| 2 quick presses (under 2 seconds) | Check mode / display last test result for 20 seconds |
| 3 quick presses (under 2 seconds) | Clear LED status flash |
Note: Manually started function and duration tests do not alter the schedule for the six month synchronised test.